PLEASE ELABORATE ABOUT CHAPTER 12

Is it required to design the total frame for chapter 12 combinations or just while designing of bracing.
SATISH KUMAR MAMIDI
SATISH KUMAR MAMIDI
Admin

Posts : 19
Join date : 2014-02-08
Age : 37
Location : HYDERABAD

http://www.pebspennar.in/

Back to top Go down

chapter 12 (IS:800-2007) Empty Re: chapter 12 (IS:800-2007)

Post by shah Fri Feb 28, 2014 5:44 pm


FEW BASIC CONCEPT TO BE CHECKED WHILE DESIGNING CHAPTER-12 AS PER IS:800-2007

IS:800-2007, LOAD COMBINATION SHOULD BE AS PER CLAUSE 12.2.3 (PAGE NO. 87)
1.2DL + 0.5ILL + 2.5EL
0.9DL + 2.5EL

*********************************************************

CONNECTION MUST BE AS PER CLAUSE 12.4.1 (PAGE NO. 87)
For connection High Strength Friction Grip (HSFG) Bolt must be considered

***********************************************************

BRACING AS PER CLAUSE 12.7.2.1 (PAGE NO. 88)
Slenderness of bracing member should not exceed 120 (most probably it will satisfy in tube bracing only).

If we are checking for compressive strength of bracing member then it shall not exceed 0.8times the Design strength in axial compression as per clause 12.7.2.2.

as per clause 12.7.2.4 the provided bracing must not be slender member, it should be either
plastic , compact or semi-compact.

for aircraft hanger buildings as per clause 12.8.2.2 the slenderness limit of the bracing member should not exceed 160.

V-type & K-type bracing shall not permit in chapter-12, only X-Bracing or portal bracing is permitted for earth quake resistance.

COLUMN BASE
as per clause 12.12.1, Fixed column bases and their anchor bolts should be designed to withstand a moment of 1.2times of the full plastic moment capacity of the column section.

the anchor bolt shall be designed to withstand the combined shear and tension check.

***********************************************************

If anyone wants to tell something more regarding chapter-12 please .......

don't think that i hav gathered all points from code, ofcourse i gathered from code only bcoz we design the bldg as per code only.

hope everyone will share their knowledge on this forum.

thanks to mamidi who gave us good idea to share the knowledge....

shah

Posts : 1
Join date : 2014-02-28

Back to top Go down

chapter 12 (IS:800-2007) Empty Re: chapter 12 (IS:800-2007)

Post by Nithin Thu Mar 06, 2014 11:57 am

Grt answer .... Shah ji

Nithin

Posts : 4
Join date : 2014-03-06

Back to top Go down

chapter 12 (IS:800-2007) Empty Re: chapter 12 (IS:800-2007)

Post by Sponsored content


Sponsored content


Back to top Go down

Back to top


 
Permissions in this forum:
You cannot reply to topics in this forum